Relay type
OA 5669
1. 0
Relay coil
1. 1 Nominal voltage
1. 2 Nominal consumption
DC V
W
5, 6, 12, 20, 24, 48, 60, 110
0,7
2. 0
Contacts
2. 1 Contact arrangement
1 NC / 1NO
2 changeover contacts, 1 No and 1 changeover contact
AgCdO + 0,2
μ
m Au; AgNi 10 + 0,2
μ
m Au optionally + 5
μ
m Au
250
AC/DC 10 / DC 250, AC 400 (AC/DC 100 mV / 60 V)
1)
2 x 5 (see operating voltage limit curve)
10mA
3)
/ 8 (1 mA / 0,3 A)
1)
3 / 2 000 (1 mVA / 7 VA)
1)
2. 2 Contact material
2. 3 Rated insulation voltage
Switching voltage min./max.
2. 4 Limiting continuous current
Switching current min./max.
2. 5 Switching power min./max.
Switching power min./max. W 3 / 200 (1 mW / 7 W)
1)
(s. limit curve for arc-free operation)
2. 6 Switching capacity
to IEC/EN 60 947-5-1 AC 15
AC V/A
DC 13
DC V/A
2. 7 Electrical life
2)
AC 230 V 6 A cos
= 1
switching cycles
2. 8 Switching frequency max. switching cycles / s
2. 9 Response time / Release time
ms
2.10 Contact force NO / NC
cN
AC V
V
A
A
VA
NC: 230 / 1 NO: 230 / 3
NC: 24 / 2
at 1 s On, 1 s Off
> 1 x 10
5
AgNi 10
10
≤
15 /
≤
12
≥
10 /
≥
8
NO: 24 / 2
(s. contacts service life)
> 2 x 10
5
AgCdO
3. 0 Other
3. 1 Mechanical life
3. 2 Temperature range
3. 3 Degree of protection, housing
3. 4 Housing
3. 5 Vibration resistance
3. 6 Climate resistance
3. 8 Insolation according to IEC 60 664-1, EN 50 178
Rated insulation voltage
Contamination level
Overvoltage category
switching cycles
°
C
≥
50 x 10
6
- 40 ... + 60 mounted without distance (I
= 2 x 5 A)
IP40 / IP67 IEC/EN 60 529 wash proof
Thermoplast GF, PA
10 ... 55 Hz; 0,35 mm amplitude; 5 g max. IEC/EN 60 068-2-6
40 / 060 / 04 (climate category); A/B/D IEC/EN 60 068-1
double and reinforced insulation
AC V
250
2
III
Safety relay
OA / OW 5669
All technical data in this list relate to the state at the moment of edition.
We reserve the right for technical improvements and changes at any time.
according to EN 50 205, IEC/EN 60 255,
IEC 60 664-1
with positively driven contacts
wash proof model as option
double and reinforced insultaion between
contact sets according to EN 50 178
low rated power consumption
high mechanical service life
compact size, small height
Approvals: UL, CSA,
TüV approval: R 9012316
Applications:
ZH1/457 press controls
Switchgear for safety technology
OA/ OW 5669 / 25.02.03 d
Technical data
OA / OW 5669
1)
Values for AgNi 10-contacts + 5
μ
m Au
2)
10 A total current at t = 20°C and coil voltage UN
3)
Typical values