Specifications
FX0N-60
MR-DS
FX0N-60
MR-ES/UL
FX0N-60
MT-DSS
Electrical data
Integrated inputs/outputs
60
Power
supply
AC range (+10%, -15%)
—
100–240 V AC
—
Frequency at AC
Hz —
50/60 (±10 %)
—
DC range (+20%, -15%)
24 V DC
—
24 V DC
Max. input apparent power
24W
60 VA
24W
Inrush
current at ON
100 V AC
—
30 A / 5 ms
—
200 V AC
—
50 A / 5 ms
—
24 V DC
60 A / 50
s—
60 A / 50
s
Allowable momentary power failure time
10
Externalservicepowersupply(24VDC)
mA —
200
—
Inputs
Integrated inputs
36
Min. current for logical 1
mA 3.5
3.5
Max. current for logical 0
mA 1.5
1.5
Response time
For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms
Outputs
Integrated outputs
24
Output type
Relay
Transistor
Max. switching voltage
V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A 2
2
0.5
- per group*
A —
—
0.8
Max. switching
power
- inductive load
VA 80
80
12
- lamp load
W 100
100
1.5
Response time
ms 10
10
< 0.2
Life of contacts (switching times)
For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight
kg 0.9
0.9
Dimensions (W xHxD)
mm 185 x90 x 87
185 x 90 x 87
Order information
Art. no. 66663
66662
66664
* This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.
Specifications of Base Units
FX0N ¨ FX2N
MELSEC FX0N/FX2N
Specifications
BASE UNITS
BASICS
X
FX
F
MITSUBISHI ELECTRIC
27