Specifications
FX2N-16
EX-ES/UL
FX2N-16
EYR-ES/UL
FX2N-16
EYT-ES/UL
Electrical data
Integrated inputs/Outputs
16
Power supply
All modulare extension units are supplied by the base unit.
Inputs
Integrated inputs
16
—
Min. current for logical 1
mA 3,5
—
Max. current for logical 0
mA 1,5
—
Response time
For all base units of the MELSEC FX2N series values:10 ms (at time of shipment)
Outputs
Integrated outputs
—
16
Output type
—
Relay
Transistor
ON voltage (max.)
V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output
current
- per output
A —
2
0,5
- per group*
A —
—
0,8
Max. switching
power
- inductive load
VA —
80
12
-lamp load
W —
100
1,5
Response time
ms —
10
< 0,2
Life of contacts (switching times)
—
Same as base unit
—
Mechanical data
Weight
kg 0,3
0,3
Dimensions (W x H x D)
mm 40x90x87
40 x 90 x 87
Order information
Art. no. 65776
65580
65581
* This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.
Modular Extension Units
FX0N FX2N
OUT
MELSEC FX0N/FX2N
Specifications
EXTENSION UNITS
Extension Units FX2N
The FX2N series modular extension units are
available with 16 input/output points.
It is possible to choose between relay and
transistor output type.
Special features:
LEDs for indicating the input and output
status
MELSEC FX0N series compatible
Especially compact design
Vertical mounted terminal blocks with
a cable guide to the upper or lower side
BASICS
X
FX
F
MITSUBISHI ELECTRIC
35